Ground Source Heat Pump Unit Exporter

Origin: China
Application: Commercial
Category: Water Heater Pump
Payment Terms: TT , LC , Others
> Features > Parameters > Catalog

Description

34 sizes available ranging from 130kW to 4180kW cooling capacity.


Acting as multi-function unit such as cooling, heating, sanitary hot water separately or simultaneously.


Wide application as hotel, apartment, villa, factory, shopping center, office building, school, etc.


Semi- hermetic screw compressor for the whole range. Each compressor is equipped with a crankcase heater and a built-in electronic protection with temperature sensor located directly in the motor winding and on the discharge line.


The refrigerant circuit is complete with sight glass, filter drier, high and low pressure gauges, solenoid valve, electronic expansion valve, high and low pressure switch.


Shell and tube dry expansion type condenser, factory insulated with flexible close cell material.

  

Shell and tube evaporator, higher efficiency less water consumption, easy maintenance and cleaning, factory insulated with flexible close cell material.


The electric panel consists of compressor breaker, compressor contactor, phase sequence relay, control circuit breaker, microprocessor control with function display.


LCD display, touch screen control panel as standard.


Automatic operation dramatically reducing maintenance cost thanks to reliable microprocessor system.


An infinitely variable capacity control system that is capable of exactly matching the demand requirement of the system is to be supplied. This system is to provide precise and stable control of supply water temperature over the complete range of operating conditions.


Optional

Desuperheater as optional.

Electronic controller with BMS system.


Technical Data

Model Unit WW130 WW170 WW200 WW240 WW260 WW280 WW310 WW360 WW380 WW420
Cooling capacity* kW 130 170 200 240 260 280 310 360 380 420
Heating capacity* kW 127 167 196 235 255 274 304 353 372 412
Power supply 380-415V/3Ph/50Hz
Compressor
Qty/refrigerant circuit Nr. 1/1 1/1 1/1 1/1 1/1 1/1 1/1 1/1 1/1 1/1
Cooling power input* kW 24 31 37 44 48 52 57 67 70 78
Heating power input* kW 43 56 66 80 86 93 103 120 126 140
Energy adjustment steps step 25% – 100%
Max. current for wiring A 87 108 128 165 165 165 165 185 185 258
Refrigerant charge kg 23 30 36 43 46 50 55 64 68 75
Evaporator
Water side pressure drop kPa 42 45 45 45 45 46 46 46 47 46
Pipe size mm DN65 DN80 DN100 DN100 DN100 DN100 DN100 DN125 DN125 DN125
Water flow rate in cooling* m3/h 22 29 34 41 45 48 53 62 65 72
Water flow rate in heating* m3/h 9 12 14 17 18 19 22 25 26 29
Condenser
Water side pressure drop kPa 42 45 44 44 45 45 44 44 44 42
Pipe size mm DN80 DN80 DN100 DN100 DN100 DN100 DN100 DN125 DN125 DN125
Water flow rate in cooling* m3/h 12 16 19 22 24 26 29 33 35 39
Water flow rate in heating* m3/h 22 29 34 40 44 47 52 61 64 71
Dimensions
Length mm 2635 2760 2740 2880 2870 2870 2970 3170 3280 3280
Width mm 1090 1115 1175 1125 1125 1125 1230 1200 1285 1285
Height mm 1625 1555 1650 1645 1685 1685 1685 1685 1805 1805
Net weight kg 1600 1800 1900 2000 2100 2200 2250 2400 3000 3100
Noise level** dB(A) 68 69 69 70 70 72 73 73 73 73


Model Unit WW480 WW530 WW610 WW680 WW710 WW760 WW860 WW960 WW1000 WW1120
Cooling capacity* kW 480 530 610 680 710 760 860 960 1000 1120
Heating capacity* kW 470 519 598 666 696 745 843 941 980 1098
Power supply 380-415V/3Ph/50Hz
Compressor
Qty/refrigerant circuit Nr. 1/1 1/1 1/1 1/1 2/2 2/2 2/2 2/2 2/2 2/2
Cooling power input* kW 89 98 113 126 131 141 159 178 185 207
Heating power input* kW 159 176 203 226 236 252 286 319 332 372
Energy adjustment steps step 25% – 100% 12.5% – 100%
Max. current for wiring A 302 302 357 378 2×185 2×185 2×258 2×258 2×302 2×302
Refrigerant charge kg 85 94 108 121 126 135 153 171 178 199
Evaporator
Water side pressure drop kPa 46 46 46 47 47 46 47 46 46 46
Pipe size mm DN125 DN125 DN125 DN150 DN150 DN150 DN150 DN200 DN200 DN200
Water flow rate in cooling* m3/h 83 91 105 117 122 131 148 165 172 193
Water flow rate in heating* m3/h 33 37 42 47 49 53 60 67 70 78
Condenser
Water side pressure drop kPa 42 42 44 42 44 42 44 42 44 44
Pipe size mm DN125 DN125 DN125 DN150 DN125 DN125 DN125 DN125 DN125 DN150
Water flow rate in cooling* m3/h 44 49 57 63 66 70 80 89 93 104
Water flow rate in heating* m3/h 81 89 103 115 120 128 145 162 169 189
Dimensions
Length mm 3505 3505 3505 3520 4005 4505 4505 4505 4560 4560
Width mm 1280 1315 1375 1380 1415 1415 1415 1415 1460 1460
Height mm 1970 1990 1980 1980 1975 2000 2000 2000 2090 2090
Net weight kg 3500 3800 4000 4100 4210 4400 4740 5600 6600 6800
Noise level** dB(A) 74 74 74 73 74 74 74 74 74 74


Model Unit WW1200 WW1250 WW1360 WW1470 WW1720 WW1840 WW2000 WW2350 WW2500
Cooling capacity* kW 1200 1250 1360 1470 1720 1840 2000 2350 2500
Heating capacity* kW 1176 1225 1333 1441 1686 1803 1960 2303 2450
Power supply 380-415V/3Ph/50Hz
Compressor
Qty/refrigerant circuit Nr. 2/2 2/2 2/2 4/4 4/4 4/4 4/4 4/4 4/4
Cooling power input* kW 222 231 252 272 319 341 370 435 463
Heating power input* kW 399 415 452 488 571 611 664 781 831
Energy adjustment steps step 12.5% – 100% 6.25% – 100%
Max. current for wiring A 2×357 2×357 2×378 4×185 4×258 4×258 4×302 4×357 4×357
Refrigerant charge kg 213 222 242 261 306 327 356 418 444
Evaporator  
Water side pressure drop kPa 46 46 46 45 45 46 46 47 47
Pipe size mm DN200 DN200 DN200 2×DN150 2×DN150 2×DN200 2×DN200 2×DN200 2×DN200
Water flow rate in cooling* m3/h 206 215 234 253 296 316 344 404 430
Water flow rate in heating* m3/h 84 87 95 102 120 128 139 164 174
Condenser  
Water side pressure drop kPa 44 42 45 52 52 52 52 52 52
Pipe size mm DN150 DN150 DN150 2×DN200 2×DN200 2×DN200 2×DN200 2×DN200 2×DN200
Water flow rate in cooling* m3/h 111 116 126 136 159 170 185 218 232
Water flow rate in heating* m3/h 202 211 229 248 290 310 337 396 421
Dimensions  
Length mm 4660 4660 4660 4600 4650 4690 4730 4780 4800
Width mm 1585 1585 1585 2250 2270 2300 2340 2380 2400
Height mm 2215 2215 2240 2350 2380 2410 2450 2470 2500
Net weight kg 7000 7400 8000 8800 9000 9800 11600 12300 13000
Noise level** dB(A) 74 74 76 80 80 81 81 82 82

* Performance values refer to the following conditions:

Condenser water inlet/outlet temperature: 30ºC/35ºC, evaporator water inlet/outlet temperature: 12ºC/7ºC.     

** Noise level measured in free field condition at distance of 1 meter.